Multi-turn actuators

Weather-proof SA & SAR actuators with SIL controls

AUMA India SA/SAR actuator with SIL capability are specifically designed for the functional safety with safety integrity level upto - SIL 3 suitable for highest safety requirements in accordance with IEC 61508:2010 standard.

The actuators come with advanced control technology, world-calss quality for meeting the stringent SIL specification. The actuators are equipped with an absolute encoder for the accurate direct measurement of limit & torque and an additional SIL module specially designed for the execution of the safety functions along with additional limit switches. In case of an emergency at the plant and when requesting a safety function, the standard logic of actuator controls is by-passed and the safety function is performed via the SIL module. Consequently, the safety function always overrules standard operation. 

Actuators SA3 – SA100 for Open-close duty with SIL controls are rated for short-time duty S2 - 15 min. 

Actuators SAR3 – SAR100 with SIL controls are designed for modulating or regulating duty S4 - 25%. 

Auma India SA/SAR actuators with SIL controls are certified by TUV Nord for use in safety systems with following suitable safety functions in case of emergency:

  • Safe OPEN/CLOSE
  • Safe STOP
  • Safe end position feedback 

Design features SA

  • Torque range from 30 Nm to 1000 Nm
  • Output speeds from 4 to 180 rpm
  • Available with 3-ph AC motors
  • Non-intrusive actuator (limit and torque) setting and control programming
  • Local controls with lockable selector switch, push-buttons and indication lights
  • LCD for status indication and programming support
  • Motor control via reversing contactors or thyristors
  • Hand wheel for manual operation

Design features SA

  • Torque range from 30 Nm to 1000 Nm
  • Modulating range from 20 Nm to 500 Nm
  • Maximum number of starts 1,200 c/h with motor power up to 0.55 kW
  • Output speeds from 4 to 45 rpm
  • Available with 3-ph AC motors
  • Non-intrusive actuator (limit and torque) setting and control programming
  • Local controls with lockable selector switch, push-buttons and indication lights
  • LCD for status indication and programming support
  • Motor control via reversing contactors or thyristors
  • Hand wheel for manual operation

Interfaces

  • Control inputs with different voltages (AC)
  • Potential-free signal relays for status indication
  • Analogue control (0/4-20 mA)
  • Freely definable intermediate positions
  • Fieldbus control (Profibus DP, Modbus RTU, Modbus TCP)
  • Limit and torque as analogue Signal
    (in connection with magnetic limit and torque transmitter MWG)
  • Bluetooth interface to notebook and Android tablet
  • Functional safety: Up to SIL 3 in selected configurations ("1oo2")

Ambient conditions

  • Enclosure protection: IP 68
  • High quality corrosion protection as per EN ISO 12944-2. Option: Special corrosion protection on request.
  • Ambient Temperature: -20 deg C to +70 deg C
  • Relative humidity: Up to 100%

Interfaces

  • Electrical connection via 64 pin plug & socket non modular double sealing connector
  • Profibus DP termination card for fieldbus communication
  • Optional parking frame for safe storage of a disconnected plug or cover to protect against touching the bare contacts and against environmental influences.
  • Output drive types according to ISO 5210 and DIN 3210 standard
  • Cable glands in different versions:
    • Standard : Metric
    • Optional : BSC, NPT

Functional Safety - SIL

  • TÜV certified in compliance with IEC 61508
  • An absolute encoder for the accurate direct measurement of limit & torque
  • An additional SIL module specially designed for the execution of the safety functions along with additional limit switches
  • Safety functions: Safe OPEN/Safe CLOSE, Safe STOP, Safe end position feedback
  • Versions: Profibus / MODBUS interface, 4-20mA command signal and hardwired interface.
  • Control of safety functions via wirebreak-proof (low active) 24 V DC inputs, redundant application for ESD function

Approvals

  • TUV Nord certified for the architectural configuration up to SIL3
  • Profibus device certificate for epac controls for Profibus DP V0/V1

Specifications

Key information at a glance